BS EN 60947-2:2006+A2:2013
$215.11
Low-voltage switchgear and controlgear – Circuit-breakers
Published By | Publication Date | Number of Pages |
BSI | 2013 | 236 |
This standard applies to circuit-breakers, the main contacts of which are intended to be connected to circuits, the rated voltage of which does not exceed 1 000 V a.c. or 1 500 V d.c.; it also contains additional requirements for integrally fused circuit-breakers.
It applies whatever the rated currents, the method of construction or the proposed applications of the circuit-breakers may be.
The requirements for circuit-breakers which are also intended to provide earth-leakage protection are contained in Annex B.
The additional requirements for circuit-breakers with electronic over-current protection are contained in Annex F.
The additional requirements for circuit-breakers for IT systems are contained in Annex H.
The requirements and test methods for electromagnetic compatibility of circuit-breakers are contained in Annex J.
The requirements for circuit-breakers not fulfilling the requirements for over-current protection are contained in Annex L.
The requirements for modular residual current devices (without integral current breaking device) are contained in Annex M.
The requirements and test methods for electromagnetic compatibility of circuit-breaker auxiliaries are contained in Annex N.
Supplementary requirements for circuit-breakers used as direct-on-line starters are given in IEC 60947-4-1, applicable to low-voltage contactors and starters.
The requirements for circuit-breakers for the protection of wiring installations in buildings and similar applications, and designed for use by uninstructed persons, are contained in IEC 60898.
The requirements for circuit-breakers for equipment (for example electrical appliances) are contained in IEC 60934.
For certain specific applications (for example traction, rolling mills, marine service) particular or additional requirements may be necessary.
NOTE Circuit-breakers which are dealt with in this standard may be provided with devices for automatic opening under predetermined conditions other than those of over-current and undervoltage as, for example, reversal of power or current. This standard does not deal with the verification of operation under such pre-determined conditions.
The object of this standard is to state:
-
the characteristics of circuit-breakers;
-
the conditions with which circuit-breakers shall comply with reference to:
-
operation and behaviour in normal service;
-
#operation and behaviour in case of overload and operation and behaviour in case of short-circuit, including co-ordination in service (selectivity and back-up protection);#
-
dielectric properties;
-
-
tests intended for confirming that these conditions have been met and the methods to be adopted for these tests;
-
information to be marked on or given with the apparatus.
PDF Catalog
PDF Pages | PDF Title |
---|---|
6 | CONTENTS |
11 | 1 General 1.1 Scope and object |
12 | 1.2 Normative references |
14 | 2 Definitions |
17 | 3 Classification |
18 | 4 Characteristics of circuit-breakers 4.1 Summary of characteristics |
19 | 4.2 Type of circuit-breaker 4.3 Rated and limiting values of the main circuit |
21 | Table 1 โ Standard ratios between Ics and Icu |
22 | Table 2 โ Ratio n between short-circuit making capacity and short-circuit breaking capacity and related power factor (for a.c. circuit-breakers) Table 3 โ Minimum values of rated short-time withstand current |
23 | 4.4 Utilization categories 4.5 Control circuits Table 4 โ Utilization categories Table 5 โ Preferred values of the rated control supply voltage, if different from that of the main circuit |
24 | 4.6 Auxiliary circuits 4.7 Releases |
25 | 4.8 Integral fuses (integrally fused circuit-breakers) 5 Product information 5.1 Nature of the information |
26 | 5.2 Marking |
27 | 5.3 Instructions for installation, operation and maintenance 6 Normal service, mounting and transport conditions 7 Constructional and performance requirements 7.1 Constructional requirements |
29 | 7.2 Performance requirements |
31 | Table 6 โ Characteristics of the opening operation of inverse time-delay over-current opening releases at the reference temperature |
33 | Table 7 โ Temperature-rise limits for terminals and accessible parts |
34 | Table 8 โ Number of operating cycles |
35 | 7.3 Electromagnetic compatibility (EMC) 8 Tests 8.1 Kind of tests |
36 | 8.2 Compliance with constructional requirements 8.3 Type tests |
38 | Table 9 โ Overall schema of test sequences |
39 | Table 9a โ Applicability of test sequences according to the relationship between Ics, Icu and Icw |
45 | Table 10 โ Number of samples for test |
47 | Table 11 โ Values of power factors and time constants corresponding to test currents |
58 | Table 12 โ Test circuit characteristics for overload performance |
66 | 8.4 Routine tests |
70 | Figure 1 โ Test arrangement (connecting cables not shown) for short-circuit tests |
71 | Annex A (normative) Co-ordination under short-circuit conditions between a circuit-breaker and another short-circuit protective device associated in the same circuit |
73 | Untitled |
76 | Figure A.1 โ Over- current co-ordination between a circuit-breaker and a fuse or back-up protection by a fuse: operating characteristics |
77 | Figure A.2 Figure A.3 โ Total discrimination between two circuit-breakers |
78 | Figure A.4 Figure A.5 โ Back-up protection by a circuit-breaker โ Operating characteristics |
79 | Figure A.6 โ Example of test circuit for conditional short-circuit breaking capacity tests showing cable connections for a 3-pole circuit-breaker (C1) |
81 | Annex B (normative) Circuit-breakers incorporating residual current protection |
86 | Table B.1 โ Operating characteristic for non-time-delay type |
87 | Table B.2 โ Operating characteristic for time-delay-type having a limiting non-actuating time of 0,06 s |
91 | Table B.3 โ Requirements for CBRs functionally dependent on line voltage |
94 | Table B.4 โ Additional test sequences |
99 | Table B.5 โ Tripping current range for CBRs in case of an earth fault comprising a d.c. component |
105 | Figure B.1 โ Test circuit for the verification of the operating characteristic (see B.8.2) |
106 | Figure B.2 โ Test circuit for the verification of the limiting value of the non-operating current under over-current conditions (see B.8.5) |
107 | Figure B.3 โ Test circuit for the verification of the behaviour of CBRs classified under B.3.1.2.2 (see B.8.9) |
108 | Figure B.4 โ Current ring wave 0,5 ยตs/100 kHz |
109 | Figure B.5 โ Example of test circuit for the verification of resistance to unwanted tripping Figure B.6 โ Surge current wave 8/20 ยตs |
110 | Figure B.7 โ Test circuit for the verification of resistance to unwanted tripping in case of flashover without follow-on current (B.8.6.2) |
111 | Figure B.8 โ Test circuit for the verification of the correct operation of CBRs, in the case of residual pulsating direct currents (see B.8.7.2.1, B.8.7.2.2 and B.8.7.2.3) |
112 | Figure B.9 โ Test circuit for the verification of the correct operation of CBRs, in the case of a residual pulsating direct current superimposed by a smooth direct residual current (see B.8.7.2.4) |
113 | Annex C (normative) Individual pole short-circuit test sequence |
114 | Annex D Vacant |
115 | Annex E (informative) Items subject to agreement between manufacturer and user |
116 | Annex F (normative) Additional tests for circuit-breakers with electronic over-current protection |
121 | Table F.1 โ Test parameters for current dips and interruptions |
125 | Figure F.1 โ Representation of test current produced by back-to-back thyristors in accordance with F.4.1 |
126 | Figure F.2 โ Test circuit for immunity and emission tests in accordance with F.4.1.3, F.4.2, F.4.3, F.4.6, F.4.7.1, F.5.4 and F.6.2 โ Two phase poles in series |
127 | Figure F.3 โ Test circuit for immunity and emission tests in accordance with F.4.1.3, F.4.2, F.4.3, F.4.6, F.4.7.1, F.5.4 and F.6.2 โ Three phase poles in series |
128 | Figure F.4 โ Test circuit for immunity and emission tests in accordance with F.4.1.3, F.4.2, F.4.3, F.4.6, F.4.7.1, F.5.4 and F.6.2 โ Three-phase connection |
129 | Figure F.5 โ Test current for the verification of the influence of the current dips and interruptions in accordance with F.4.7.1 |
130 | Figure F.6 โ Circuit for electrical fast transients/bursts (EFT/B) immunity test in accordance with F.4.4 โ Two phase poles in series |
131 | Figure F.7 โ Circuit for electrical fast transients/bursts (EFT/B) immunity test in accordance with F.4.4 โ Three phase poles in series |
132 | Figure F.8 โ Circuit for electrical fast transients/bursts (EFT/B) immunity test in accordance with F.4.4 โ Three-phase connection |
133 | Figure F.9 โ Test circuit for the verification of the influence of surges in the main circuit (line-to-earth) in accordance with F.4.5 โ Two phase poles in series |
134 | Figure F.10 โ Test circuit for the verification of the influence of surges in the main circuit (line-to-earth) in accordance with F.4.5 โ Three phase poles in series |
135 | Figure F.11 โ Test circuit for the verification of the influence of surges in the main circuit (line-to-earth) in accordance with F.4.5 โ Three-phase connection |
136 | Figure F.12 โ Test circuit for the verification of the influence of current surges in the main circuit in accordance with F.4.5 โ Two phase poles in series Figure F.13 โ Test circuit for the verification of the influence of current surges in the main circuit in accordance with F.4.5 โ Three phase poles in series |
137 | Figure F.14 โ Test circuit for the verification of the influence of current surges in the main circuit in accordance with F.4.5 โ Three-phase connection Figure F.15 โ Temperature variation cycles at a specified rate of change in accordance with F.9.1 |
138 | Figure F.16 โ General test set up for immunity tests |
139 | Figure F.17 โ Test set up for the verification of immunity to radiated r.f. electromagnetic fields |
140 | Figure F.18 โ Test set up for the verification of immunity to electrical fast transients/bursts (EFT/B) on power lines |
141 | Figure F.19 โ Test set up for verification of immunity to electrical fast transients/bursts (EFT/B) on signal lines |
142 | Figure F.20 โ General test set-up for the verification of immunity to conducted disturbances induced by r.f. fields (common mode) |
143 | Figure F.21 โ Arrangement of connections for the verification of immunity to conducted disturbances induced by r.f. fields โ Two phase poles in series configuration |
144 | Figure F.22 โ Arrangement of connections for the verification of immunity to conducted disturbances induced by r.f. fields โ Three phase poles in series configuration |
145 | Figure F.23 โ Arrangement of connections for the verification of immunity to conducted disturbances induced by r.f. fields โ Three-phase configuration |
146 | Annex G (normative) Power loss |
148 | Figure G.1 โ Example of power loss measurement according to G.2.1 Figure G.2 โ Example of power loss measurement according to G.2.2 and G.2.3 |
149 | Annex H (normative) Test sequence for circuit-breakers for IT systems |
151 | Annex J (normative) Electromagnetic compatibility (EMC) โ Requirements and test methods for circuit-breakers |
153 | Table J.1 โ EMC โ Immunity tests |
154 | Table J.2 โ Reference data for immunity test specifications |
157 | Table J.3 โ EMC โ Emission tests Table J.4 โ Reference data for emission test specifications |
159 | Figure J.1 โ EUT mounted in a metallic enclosure |
160 | Figure J.2 โ Test set up for the measurement of radiated r.f. emissions |
161 | Figure J.3 โ Test set up for the verification of immunity to electrostatic discharges |
162 | Figure J.4 โ Test set up for the verification of immunity to radiated r.f. electromagnetic fields |
163 | Figure J.5 โ Test set up for the verification of immunity to electrical fast transients/bursts (EFT/B) on power lines |
164 | Figure J.6 โ Test set up for the verification of immunity to electrical fast transients/bursts (EFT/B) on signal lines |
165 | Annex K (informative) Glossary of symbols related to products covered by this standard |
167 | Figure K.1 โ Relationship between symbols and tripping characteristics |
174 | Annex L (normative) Circuit-breakers not fulfilling the requirements for overcurrent protection |
179 | Annex M (normative) Modular residual current devices (without integral current breaking device) |
185 | Table M.1 โ Product information |
187 | Table M.2 โ Requirements for MRCDs with voltage source |
189 | Table M.3 โ Test sequences |
203 | Figure M.1 โ Test circuits for the verification of operation in the case of a steady increase of residual current |
204 | Figure M.2 โ Test circuits for the verification of operation in the case of a sudden appearance of residual current (with breaking device) |
205 | Figure M.3 โ Test circuits for the verification of operation in the case of a sudden appearance of residual current (without breaking device) |
206 | Figure M.4 โ Test circuits for the verification of the limiting value of non-operating current under overcurrent conditions |
207 | Figure M.5 โ Test circuits for the verification of the resistance to unwanted tripping in the case of loading of the network capacitance |
208 | Figure M.6 โ Test circuit for the verification of the resistance to unwanted tripping in the case of flashover without follow-on current |
209 | Figure M.7 โ Test circuits for the verification of operation in the case of a continuous rise of a residual pulsating direct current |
210 | Figure M.8 โ Test circuits for the verification of operation in the case of a sudden appearance of residual pulsating direct current (without breaking device) |
211 | Figure M.9 โ Test circuits for the verification of operation in the case of a sudden appearance of residual pulsating direct current (with breaking device) |
212 | Figure M.10 โ Test circuits for the verification of operation in the case of a residual pulsating direct current superimposed by smooth direct current of 6 mA |
213 | Figure M.11 โ Test circuits for the verification of operation in the case of a slowly rising residual smooth direct current |
214 | Figure M.12 โ Test circuits for the verification of operation in the case of a sudden appearance of residual smooth direct current (without breaking device) |
215 | Figure M.13 โ Test circuits for the verification of operation in the case of a sudden appearance of residual smooth direct current (with breaking device) |
216 | Figure M.14 โ Test circuits for the verification of operation in the case of a slowly rising residual current resulting from a fault in a circuit fed by a three-pulse star or a six-pulse bridge connection |
217 | Figure M.15 โ Test circuits for the verification of operation in the case of a slowly rising residual current resulting from a fault in a circuit fed by a two-pulse bridge connection line-to-line |
218 | Figure M.16 โ Test circuit for the verification of the behaviour of MRCDs with separate sensing means in the case of a failure of the sensor means connection |
219 | Figure M.17 โ Test circuit for the verification of the behaviour of MRCD with separate sensing means under short-circuit conditions |
220 | Figure M.18 โ Test circuit for the verification of the behaviour of MRCD with integral sensing means under short-circuit conditions |
221 | Figure M.19 โ Test circuit for the verification of the behaviour of terminal type MRCD under short-circuit conditions |
222 | Figure M.20 โ Verification of immunity to radiated r.f. electromagnetic fields โ Test set-up for MRCD with separate sensing means (additional to the test of Annex B) |
223 | Figure M.21 โ Verification of immunity to electrical fast transients/bursts (EFT/B) on the sensing means connection of an MRCD with separate sensing means (additional to the test of Annex B) Figure M.22 โ Verification of immunity to conducted disturbances induced by r.f. fields โ Test set up for MRCD with separate sensing means (additional to the test of Annex B) |
224 | Annex N (normative) Electromagnetic compatibility (EMC) โ Additional requirements and test methods for devices not covered by Annexes B, F and M |
228 | Annex O (normative) Instantaneous trip circuit-breakers (ICB) |
231 | Bibliography |