ASHRAE 137 09:2009 Edition
$29.25
ASHRAE Standard 137-2009 Methods of Testing for Efficiency of Space-Conditioning/Water-Heating Appliances that Include a Desuperheater Water Heater (ANSI/ASHRAE Approved)
Published By | Publication Date | Number of Pages |
ASHRAE | 2009 | 46 |
PDF Catalog
PDF Pages | PDF Title |
---|---|
4 | 1. PURPOSE 1. PURPOSE 1.1 This standard provides test methods and calculation procedures for establishing the efficiencies of space-conditioning/ water-heating appliances having refrigerant-to-water desuperheaters. 1.1 This standard provides test methods and calculation procedures for establishing the efficiencies of space-conditioning/ water-heating appliances having refrigerant-to-water desuperheaters. 1.2 The procedures may be used as a basis for establishing efficiency ratings for such equipment and for estimating annual energy consumption. 1.2 The procedures may be used as a basis for establishing efficiency ratings for such equipment and for estimating annual energy consumption. 2. SCOPE 2. SCOPE 3. DEFINITIONS 3. DEFINITIONS |
5 | 4. NOMENCLATURE 4. NOMENCLATURE |
9 | 5. CLASSIFICATIONS 5. CLASSIFICATIONS 6. REQUIREMENTS 6. REQUIREMENTS 6.1 Seasonal Energy Efficiency Ratio (SEER). The SEER of the combined appliance shall be determined from the tests and the calculation procedure described in ANSI/ASHRAE Standard 116, Methods of Testing for Rating Seasonal Efficiency of Unitary Air C… 6.1 Seasonal Energy Efficiency Ratio (SEER). The SEER of the combined appliance shall be determined from the tests and the calculation procedure described in ANSI/ASHRAE Standard 116, Methods of Testing for Rating Seasonal Efficiency of Unitary Air C… 6.2 Heating Seasonal Performance Factor (HSPF). The HSPF of the combined appliance shall be determined from the tests and the calculation procedure described in ANSI/ ASHRAE Standard 116,1 supplemented by the additional provisions of Sections 7 throu… 6.2 Heating Seasonal Performance Factor (HSPF). The HSPF of the combined appliance shall be determined from the tests and the calculation procedure described in ANSI/ ASHRAE Standard 116,1 supplemented by the additional provisions of Sections 7 throu… 6.3 Energy Factor (EF). The energy factor of the electric water heater shall be determined in accordance with ANSI/ ASHRAE Standard 118.2, Method of Testing for Rating Residental Water Heaters.2 6.3 Energy Factor (EF). The energy factor of the electric water heater shall be determined in accordance with ANSI/ ASHRAE Standard 118.2, Method of Testing for Rating Residental Water Heaters.2 6.4 Combined Space-Conditioning and Water-Heating Performance. For each season, the space-conditioning and water-heating performance of the combined appliance shall be determined using the calculations prescribed in Section 11. 6.4 Combined Space-Conditioning and Water-Heating Performance. For each season, the space-conditioning and water-heating performance of the combined appliance shall be determined using the calculations prescribed in Section 11. 7. INSTRUMENTATION SPECIFICATIONS 7. INSTRUMENTATION SPECIFICATIONS 7.1 Temperature Measurements 7.1 Temperature Measurements TABLE 1 Component Assemblies Constituting a Combined Appliance TABLE 1 Component Assemblies Constituting a Combined Appliance 7.2 Pressure Measurements 7.2 Pressure Measurements 7.3 Airflow Measurements 7.3 Airflow Measurements 7.4 Electrical Power, Energy, and Voltage Measurements 7.4 Electrical Power, Energy, and Voltage Measurements |
10 | 7.5 Desuperheater Water Flow Rate. For active systems that are tested using Type A water-heating-mode tests, the water flow rate through the desuperheater shall be measured using a flowmeter. The flow rate measurement () shall be accurate to within 7.5 Desuperheater Water Flow Rate. For active systems that are tested using Type A water-heating-mode tests, the water flow rate through the desuperheater shall be measured using a flowmeter. The flow rate measurement () shall be accurate to within 7.6 Water Mass or Volume Measurements. During the simulated use test and Type B water-heating-mode tests, either the mass or volume of the water withdrawn from the water heater is measured. If a mass measurement is used, the scale shall be accurate t… 7.6 Water Mass or Volume Measurements. During the simulated use test and Type B water-heating-mode tests, either the mass or volume of the water withdrawn from the water heater is measured. If a mass measurement is used, the scale shall be accurate t… 7.7 Time Measurements. The elapsed time measurements shall be made using an instrument that is accurate to within ±0.3% of the reading. 7.7 Time Measurements. The elapsed time measurements shall be made using an instrument that is accurate to within ±0.3% of the reading. 8. APPARATUS 8. APPARATUS 8.1 Test Apparatus 8.1 Test Apparatus |
11 | 8.2 Standard Components. If the manufacturer neither supplies nor specifies the heat pump (air conditioner), water heater, or water pump (if required), then components meeting the criteria listed below shall be used for testing. 8.2 Standard Components. If the manufacturer neither supplies nor specifies the heat pump (air conditioner), water heater, or water pump (if required), then components meeting the criteria listed below shall be used for testing. Figure 1 Physical specifications required of the standard water heater. Figure 1 Physical specifications required of the standard water heater. |
12 | 8.3 Installation of the Appliance and Instrumentation 8.3 Installation of the Appliance and Instrumentation Figure 2 Default installation requirements for field- installed desuperheaters: (a) passive systems and (b) insert systems. Figure 2 Default installation requirements for field- installed desuperheaters: (a) passive systems and (b) insert systems. |
14 | Figure 3 Examples of acceptable instrumentation locations and piping arrangements for the water heater inlet and outlet. Figure 3 Examples of acceptable instrumentation locations and piping arrangements for the water heater inlet and outlet. |
15 | Figure 3 (cont.) Examples of acceptable instrumentation locations and piping arrangements for the water heater inlet and outlet. Figure 3 (cont.) Examples of acceptable instrumentation locations and piping arrangements for the water heater inlet and outlet. |
16 | Figure 4 Location of internal tank temperature sensors. Figure 4 Location of internal tank temperature sensors. Figure 5 Default water piping connections at the water heater: (a) fixed-flow active systems and (b) variable- flow active systems. Figure 5 Default water piping connections at the water heater: (a) fixed-flow active systems and (b) variable- flow active systems. |
18 | Figure 6a Acceptable test setup for water-heating-mode tests conducted using the Type A water-heating-mode test method: water heater and desuperheater are not packaged. Figure 6a Acceptable test setup for water-heating-mode tests conducted using the Type A water-heating-mode test method: water heater and desuperheater are not packaged. Figure 6b Acceptable test setup for water-heating- mode tests conducted using the Type A water-heating- mode test method: water heater and desuperheater are packaged. Figure 6b Acceptable test setup for water-heating- mode tests conducted using the Type A water-heating- mode test method: water heater and desuperheater are packaged. 8.4 Test Setup 8.4 Test Setup |
19 | 9. METHODS OF TEST 9. METHODS OF TEST 9.1 Primary Test Methods 9.1 Primary Test Methods |
20 | 9.2 Secondary Test Methods 9.2 Secondary Test Methods |
21 | 10. TEST PROCEDURE 10. TEST PROCEDURE 10.1 General 10.1 General |
22 | 10.2 Test Requirements and Test Conditions 10.2 Test Requirements and Test Conditions TABLE 2a Summary of Laboratory Tests and Test Conditions Associated with the Space-Cooling Season TABLE 2a Summary of Laboratory Tests and Test Conditions Associated with the Space-Cooling Season TABLE 2b Summary of Laboratory Tests and Test Conditions Associated with the Space-Heating Season TABLE 2b Summary of Laboratory Tests and Test Conditions Associated with the Space-Heating Season |
23 | 10.3 Tests Tolerances and Energy Balance Requirements 10.3 Tests Tolerances and Energy Balance Requirements 10.4 Water Heater Volume Determination. The volume of the water heater, Vt , shall be determined either via a direct volume measurement or two mass measurements. If using the latter approach, the mass of the water heater shall be measured when empty … 10.4 Water Heater Volume Determination. The volume of the water heater, Vt , shall be determined either via a direct volume measurement or two mass measurements. If using the latter approach, the mass of the water heater shall be measured when empty … 10.5 Simulated Use Test 10.5 Simulated Use Test TABLE 3a Test Tolerances for the Simulated Use Test TABLE 3a Test Tolerances for the Simulated Use Test |
24 | TABLE 3b Test Tolerances for Type A Water-Heating-Mode Tests TABLE 3b Test Tolerances for Type A Water-Heating-Mode Tests TABLE 3c Test Tolerances for Type B Water-Heating-Mode Tests TABLE 3c Test Tolerances for Type B Water-Heating-Mode Tests |
27 | 10.6 Space-Conditioning-Only-Mode Tests. The space- conditioning-only tests shall be conducted with the desuperheater and water heater installed in accordance with Section 8.3 and filled with water. For active systems, the water pump shall be disable… 10.6 Space-Conditioning-Only-Mode Tests. The space- conditioning-only tests shall be conducted with the desuperheater and water heater installed in accordance with Section 8.3 and filled with water. For active systems, the water pump shall be disable… 10.7 Water-Heating-Mode Tests (COOL&WH and HEAT&WH). For water-heating-mode tests, space- conditioning capacity and electrical power shall be determined using the same test apparatus and, except for very few additions, the same test procedures as use… 10.7 Water-Heating-Mode Tests (COOL&WH and HEAT&WH). For water-heating-mode tests, space- conditioning capacity and electrical power shall be determined using the same test apparatus and, except for very few additions, the same test procedures as use… |
29 | TABLE 4 Suggested Initial Target Temperatures When Conducting Type B Water-Heating-Mode Tests TABLE 4 Suggested Initial Target Temperatures When Conducting Type B Water-Heating-Mode Tests |
31 | 11. CALCULATIONS 11. CALCULATIONS 11.1 Seasonal Energy Efficiency Ratio (SEER) of the Combined Appliance When Used Only for Space Cooling. The SEER of the combined appliance shall be calculated as described in ANSI/ASHRAE Standard 116.1 The space- cooling capacities and electrical po… 11.1 Seasonal Energy Efficiency Ratio (SEER) of the Combined Appliance When Used Only for Space Cooling. The SEER of the combined appliance shall be calculated as described in ANSI/ASHRAE Standard 116.1 The space- cooling capacities and electrical po… 11.2 Heating Seasonal Performance Factors (HSPF) of the Combined Appliance When Used Only for Space Heating. An HSPF of the combined appliance shall be calculated as described in ANSI/ASHRAE Standard 116.1 The space-heating capacities and electrical … 11.2 Heating Seasonal Performance Factors (HSPF) of the Combined Appliance When Used Only for Space Heating. An HSPF of the combined appliance shall be calculated as described in ANSI/ASHRAE Standard 116.1 The space-heating capacities and electrical … 11.3 Combined Performance Factor for the Space- Cooling and Water-Heating Season (CPFcs ). The combined performance factor for the space-cooling and water- heating season shall be calculated as follows: 11.3 Combined Performance Factor for the Space- Cooling and Water-Heating Season (CPFcs ). The combined performance factor for the space-cooling and water- heating season shall be calculated as follows: |
32 | TABLE 5 Fractional Bin Hours for the Space-Cooling and Water-Heating Seasonal Calculations TABLE 5 Fractional Bin Hours for the Space-Cooling and Water-Heating Seasonal Calculations TABLE 6 Standby Losses of an Electric Water Heater as a Function of Its Energy Factor TABLE 6 Standby Losses of an Electric Water Heater as a Function of Its Energy Factor |
33 | 11.4 Combined Performance Factor for the Space- Heating and Water-Heating Season (CPFhs). The combined performance factor for the space-heating and water- heating season shall be calculated as follows: 11.4 Combined Performance Factor for the Space- Heating and Water-Heating Season (CPFhs). The combined performance factor for the space-heating and water- heating season shall be calculated as follows: |
34 | Figure 7 Map of the generalized climatic regions. Figure 7 Map of the generalized climatic regions. TABLE 7 Fractional Bin Hours and Outdoor Design Temperatures, by Region, for the Space-Heating and Water-Heating Seasonal Calculations TABLE 7 Fractional Bin Hours and Outdoor Design Temperatures, by Region, for the Space-Heating and Water-Heating Seasonal Calculations |
37 | 11.5 Combined Performance Factor for the Water- Heating-Only Season (CPFws ). For all combined appliances that incorporate a desuperheater, the combined performance factor for the water-heating-only season equals the energy factor of the water heater… 11.5 Combined Performance Factor for the Water- Heating-Only Season (CPFws ). For all combined appliances that incorporate a desuperheater, the combined performance factor for the water-heating-only season equals the energy factor of the water heater… 12. REFERENCES 12. REFERENCES A1. For the Space-Cooling and Water-Heating Season A1. For the Space-Cooling and Water-Heating Season |
38 | TABLE A1 Seasonal Operating Hours for Each Climatic Region TABLE A1 Seasonal Operating Hours for Each Climatic Region A2. For the Space-Heating and Water-Heating Season A2. For the Space-Heating and Water-Heating Season A3. For the Water-Heating-Only Season A3. For the Water-Heating-Only Season |
39 | A4. Annual Energy Consumption and Operating Cost A4. Annual Energy Consumption and Operating Cost B1. For the Space-Cooling and Water-Heating Season B1. For the Space-Cooling and Water-Heating Season B2. For the Space-Heating and Water-Heating Season B2. For the Space-Heating and Water-Heating Season |
40 | B3. For the Water-Heating-Only Season B3. For the Water-Heating-Only Season B4. Annual Energy Consumption and Operating Cost B4. Annual Energy Consumption and Operating Cost C1. For the Space-Cooling and Water-Heating Season C1. For the Space-Cooling and Water-Heating Season C2. For the Space-Heating and Water-Heating Season C2. For the Space-Heating and Water-Heating Season C3. For the Water-Heating-Only Season C3. For the Water-Heating-Only Season C4. Annual Energy and Cost Credits C4. Annual Energy and Cost Credits |
41 | D1. Limitations D1. Limitations D2. Equivalent Seasonal Energy Efficiency Ratio D2. Equivalent Seasonal Energy Efficiency Ratio D3. Equivalent Heating Seasonal Performance Factor D3. Equivalent Heating Seasonal Performance Factor D4. Equivalent Energy Factor D4. Equivalent Energy Factor D4.1 Heat Pump with Desuperheater Water Heater D4.1 Heat Pump with Desuperheater Water Heater |
42 | D4.2 Air Conditioner with Desuperheater Water Heater D4.2 Air Conditioner with Desuperheater Water Heater E1. For the Space-Cooling and Water-Heating Season E1. For the Space-Cooling and Water-Heating Season |
43 | E2. For the Space-Heating and Water-Heating Season E2. For the Space-Heating and Water-Heating Season E3. For the Water-Heating-Only Season E3. For the Water-Heating-Only Season |